胡少华,李陆军,吴襄竹,赵顺安,宋小军,宋志勇.环境风对自然通风海水冷却塔的性能影响原型观测及分析[J].中国水利水电科学研究院学报,2019,17(1):45-50
环境风对自然通风海水冷却塔的性能影响原型观测及分析
Observation and analysis of influence of cross wind on the performance of natural draft seawater cooling tower
投稿时间:2017-12-12  
DOI:10.13244/j.cnki.jiwhr.2019.01.007
中文关键词:  海水冷却塔  环境风  原型观测  热力阻力  模型试验  数值模拟
英文关键词:seawater cooling tower  cross wind  prototype observation  thermal resistance  model test  numerical simulation
基金项目:
作者单位
胡少华 深圳中广核工程设计有限公司, 广东 深圳 518057 
李陆军 中国水利水电科学研究院 水力学研究所, 北京 100038 
吴襄竹 深圳中广核工程设计有限公司, 广东 深圳 518057 
赵顺安 中国水利水电科学研究院 水力学研究所, 北京 100038 
宋小军 中国水利水电科学研究院 水力学研究所, 北京 100038 
宋志勇 中国水利水电科学研究院 水力学研究所, 北京 100038 
摘要点击次数: 4338
全文下载次数: 7111
中文摘要:
      环境风对热力阻力性能影响是海水冷却塔设计的重要问题之一,本文依据环境风对冷却塔进风口阻力系数及出口阻力系数的影响的研究成果,修正了自然通风海水冷却塔热力阻力计算程序,并分析了某大型自然通风海水冷却塔的原型观测数据。结果表明,平均风速为2.4 m/s时,出水温度实测值比设计值高0.4℃,出水温度预测值比设计值高0.3℃;在平均风速为5.2 m/s时,出水温度实测值比设计值高1.2℃,出水温度预测值比设计值高1.4℃。研究结果可为大型自然通风海水冷却塔的设计提供参考。
英文摘要:
      The influence of cross wind on heat-resistance performance is one of the most important problems in design of seawater cooling tower. Based on the study results of the model test and numerical simulation about the influence of the cross wind on the performance of the natural draft seawater cooling tower, the influence of the cross wind on the inlet and outlet drag coefficient is given, and the calculation program of thermal-resistance is revised. Based on this, the prototype observation data of a large natural draft seawater cooling tower is analyzed. The results show that,when the average wind speed is 2.4m/s,the measured value of outlet water temperature is 0.4℃ higher than the design value, and the predicted value is 0.3℃ higher than the design value; when the average wind speed is 5.2m/s, the measured value of outlet water temperature is 1.2℃ higher than the design value, and the predicted value is 1.4℃ higher than the design value. The research results can be used as a reference for the design of large natural draft seawater cooling tower.